The FA4 is a very compact, flush mounted, fully
monitored, four circuit, Fire Alarm & Control Module, developed
to protect the larger Catamaran and Mono-Hull vessels.
Good looking, compact, flush mount, modules with
sealed Touch Switch Controls for greater reliability. Easy to
use, with LED backlit, full System Status Display. Simple to install
with two 12 way plug-in terminals on the rear for connection of
ships wiring.

LED Backlit System Status
Display
Each zone is individually monitored for NORMAL
, FIRE, ISOLATE
and FAULT conditions. In addition, common
ALARM TEST and FAULT TEST
indicators, illuminate when these functions are active. The easy
to read System Status Display is backlit by colour coded LED light-bars
for instantaneous status recognition.
Compact Flush Mount
Module
The FA4 Fire Alarm Control Module is very compact. The panel facia
measures only 96 x 96 mm (less than 4 inches square). The FA4
is flush mounted with a dash cut-out size of 91 x 91 mm, and is
secured by two adjustable mounting brackets off the rear of the
module. Overall panel depth = 175 mm. All wiring terminates on
two 12 way plug in terminals on the rear of the FA4 module.
SEALED TOUCH SWITCHES
The FA4 panel facia incorporates seven sealed touch switches to
provide individual Zone Alarm Isolate and Alarm Reset functions,
Common ALARM TEST and FAULT Test Controls plus a dimmer control
of NORMAL indications for night time use.
ALARM TEST SWITCH
Pressing the ALARM TEST Switch simulates a
FIRE Alarm Condition on all four detector circuits,
to test local audible & visual alarm warnings & remote
alarm outputs. The red ALARM TEST
indication illuminates. Pressing any Isolate/Reset switch will
reset the ALARM TEST function. After testing, press each ISOL/RESET
switch twice to return all zones to the green
NORMAL condition.
FAULT
TEST SWITCH
Pressing the FAULT TEST Switch simulates a FAULT
Condition on all four detector circuits and tests local audible
and visual FAULT warnings. The amber FAULT
TEST indication also illuminates. Pressing any Isolate/Reset
switch will reset the FAULT Test function. After testing, press
each ISOL/RESET switch twice to return all zones to the green
NORMAL condition.
ISOLATE/RESET SWITCHES
The four zone ISOL/RESET Switches each perform a double isolate
function,
When pressed once, it isolates the local
audible alarms and remote alarm outputs for that zone. It resets
internal alarm and FAULT latches and resets remote fire detector
latches for that zone. The amber zone ISOLATE
indication will also illuminate. The visual alarm & FAULT
warning latches are also reset, but remain active. This serves
to verify detector operation, as it will flash the red FIRE
visual alarm immediately a detector operates, even when isolated.
Similarly, visual FAULT warnings
are reset but remain active when isolated.
When pressed a second time, The ISOL/RESET
switch again resets internal Alarm and FAULT latches and remote
fire detector latches. It re-enables the local audible alarms
and remote alarm outputs and returns that zone to the green NORMAL
condition.
DIM SWITCH
Pressing the DIM Switch dims the Green NORMAL
LED indications for night time use to assist in reducing wheelhouse
light levels as an aid to navigation.
A FIRE, FAULT or ISOLATE Status condition other
than NORMAL , is indicated at full brightness even when the Dim
Switch is active.
LED Backlit System Status Display
The four green NORMAL status indications indicate
all zones in the NORMAL ready to operate condition. The red FIRE
status indications flash a red FIRE warning when a detector on
that zone operates. The Red FIRE warning latches on internally
and remains on until isolated or reset.
The amber FAULT status indications illuminates
if a FAULT develops in that detector zone. A typical FAULT condition
would include a break or high resistance joint in the detector
zone wiring, a detector out of circuit or a low power supply voltage
that could inhibit the FIRE Alarm operation.
The amber ISOLATE
indications, indicates the Audible Alarms and Remote Alarms for
that zone are isolated.
The red ALARM TEST indication illuminates when
the ALARM TEST Switch is operated. The amber FAULT TEST indication
illuminates when the FAU LT TEST Switch is operated.
DETECTOR CIRCUITS
The four detector circuit inputs are each two
wire circuits. They will power remote detectors up to 250 mA per
circuit and are protected against excess current draw. These are
compatible with a wide range of detector types including smoke,
thermal, and flame detectors and manual switches.
An isolate/reset relay on each detector circuit
removes power to reset remote detectors each time an isolate switch
is operated.
ALARM OUTPUTS
The FA4 provides a change over, clean switched
Common Alarm Relay Output with the change over terminals accessible
to allow for all switching options.
An external link is factory fitted between terminal
16, (A 1.5 Amp protected +ve supply) and terminal 14 relay common.
This protected positive supply is switched out on terminal 13
on activation of any alarm.
An alarm load in excess of 1.5 Amp can be connected
by removing link between 14 and 16 and connect external protected
supply up to 3 Amp Max,
Four individual zone, Remote Alarm Relay Driver
Outputs (NPN @ 1.0 Amp Max) are provided. An Audible Alarm is
incorporated to provide local Fire Alarm, FAULT Warnings &
switch operation verification.
POWER SUPPLIES
The FA4 has provision for connection of two independent
DC power supplies. System will operate when either supply is active.
Power supply inputs are protected internally
from reverse polarity, over voltage, excess current draw and induced
power spikes etc.
All individual detector circuits, voltage regulators
and zone alarm outputs are protected by PCL solid state current
limiters.
The system will operate from 12 volt (when 5k
ohms EOL resistors fitted) or 24 volt (with 1 0k ohms EOL resistor
fitted). Both DC power supplies must be the same nominal voltage.
WEEKLY TESTING on a regular basis, test the
FA4 Fire Alarm & Control System.
Press the ALARM TEST switch to simulate an alarm
condition on all four detector zones. Check that all four red
visual FIRE indications illuminate and flash, and that the common
audible FIRE Alarm operates. The red ALARM TEST visual status
also illuminates.
Isolate the audible alarms for each zone by pressing
each ISOL / RESET Switch in turn, the amber zone ISOLATE Status
will illuminate.
Press each ISOL / RESET switch again to return
all zones to the green NORMAL condition.
Press the FAULT TEST Switch to simulate a FAULT
condition on all four detector Zones. Check that all four amber
visual FAULT indications illuminate accompanied by a steady audible
FAULT warning tone. The amber FAULT TEST visual status also illuminates.
Isolate the audible FAULT warnings for each zone
by pressing each ISOL / RESET Switch in turn, the amber zone ISO
LATE indications will illuminate. Press each ISOL / RESET switch
again to return all zones to the green NORMAL condition.
On a Regular Basis, check that the four green
NORMAL indications are illuminated and that the FA4 is in the
green NORMAL ready to operate condition.
FA4 -WIRING
All wiring terminates on two plug in 12 way terminals
on the rear of the FA4.
Terminal A. Is a 12 way input terminal
for two independent power supplies (12 or 24 Volt DC) and four
Fire Detector monitoring circuits.

Terminal B. Is a 12 way output terminal
with Common Alarm relay output and four individual zone alarm
outputs.

External link provides protected +ve SIDE VIEW
Dash cut out = 92 x 92 mm
1.5 Amp max, into common of alarm relay Made with Pride in Australia
|