SYSTEM DESCRIPTION:
The ITIM Systems GS-2 is a fully monitored Two Circuit
Gas Detection, Alarm and Gas Control System with remote On/Off
Gas control, bargraph display of % LEL, with audible and visual
alarms and automatic gas shutoff when a gas leak is detected.
Housed in a compact, flush mounted, display Module, it features
sealed touch switch controls for greater reliability & LED
backlit system status display for instantaneous status recognition.
|
 |
OPERATION GS-2
When Power is first switched On to the GS-2 Gas Detection &
alarm system, there will be a short WAIT delay while the sensors
warm-up to operating temperature. The SAFE LED will illuminate
when the system is operational, and detects a safe gas level at
both sensors.
Pressing the GAS On/Off switch will turn the Gas Solenoid Valve
On at the cylinder ready for cooking. GAS ON LED illuminates.
When cooking is complete, press the GAS On/Off switch again to
turn the gas off.
If a gas leak is detected,
COOKER or CYLINDER
status will Flash to identify its source. The audible and visual
alarms will latch On & the Gas Solenoid Valve will be latched
Off. The LED bargraphs show the actual Gas % LEL at each sensor.
To acknowledge & silence the alarm, press the ISOL/RESET switch
once. To reset the alarm latches and return system to normal,
press the ISOL/RESET switch again. |
GAS SENSOR ASSEMBLIES.
In a LPG cooker installation, one sensor should be mounted at
floor level beneath the cooker and one at low level in the gas
cylinder enclosure.
If used to detect gas leaks with lighter-than-air gases such as
Methane or Town Gas then the Gas
Sensor assemblies should be mounted at a high level where gas
could collect.
The gas sensing circuits are both continuously monitored for
faults. If a fault develops in a gas sensor, or the sensor wiring,
the appropriate FAULT status will illuminate, accompanied by a
steady fault tone.
TEST. Pressing the TEST switch
starts a test sequence to test all alarm and fault monitoring
functions, including alarm latches and gas shuttoff latches and
isolate and reset functions.
GAS SOLENOID VALVE. The
Gas Solenoid Valve is mounted on the gas cylinder before the regulator
and is turned on and off by operation of the Gas On/Off switch.
The system should be left in the SAFE operating condition. Manufactured
with pride in Australia in accordance with AG 601-1998 appendix
K. |